HL-2M 装置初始放电安全联锁系统研制

孙 江,夏 凡,李 波,宋 啸, 王 硕,陈宇红,胡浩天,宋显明 
  

  1. (核工业西南物理研究院,成都 610041) 
  • 收稿日期:2021-03-31 修回日期:2021-08-05 出版日期:2021-10-15 发布日期:2021-11-29
  • 作者简介:孙江(1988−),女,湖南常德人,硕士研究生,从事托卡马克装置安全联锁控制研究。
  • 基金资助:
    国家磁约束核聚变能发展研究专项(2018YFE0302104) 

Development of safety interlock system for the first plasma operation on HL-2M tokamak

SUN Jiang, XIA Fan, LI Bo, SONG Xiao, WANG Shuo,  CHEN Yu-hong, HU Hao-tian, SONG Xian-ming   

  1. (Southwestern Institute of Physics, Chengdu 610041) 

     
  • Received:2021-03-31 Revised:2021-08-05 Online:2021-10-15 Published:2021-11-29

摘要: 为确保 HL-2M 装置能安全、稳定地进行初始等离子体放电实验,参考国际热核聚变实验堆(ITER)
的安全联锁设计,并结合 HL-2M 装置的实际现状,建立了一套基于可编程逻辑控制器(PLC)慢控制的中央安全联
锁系统。搭建了一套千兆光纤星形网用来满足各系统之间的通讯。中央安全联锁系统根据故障风险等级和预先设
定的故障处理机制,协调各子系统进行联锁保护动作。WINCC 监控画面显示各子系统的运行状态和故障信息。
采用 EPICS CA 协议和 S7nodave 驱动实现了软 IOC 读取 PLC 变量,并结合 C#编程实现了对主机大厅门禁访问系
统的控制,保障了人员和设备的安全。该套中央安全联锁系统已经投入使用,平均扫描周期 1~3ms,满足 HL-2M
装置初始等离子体放电的安全联锁保护需求。

关键词: HL-2M 装置;安全联锁;PLC 

Abstract: A central safety interlock system based on PLC slow control is established to make sure the safety 
performance of the first plasma on HL-2M tokamak. The system is referred to the safety interlock design of ITER. 
A gigabit fiber star network is adopted to realize the communication between the systems. The central safety 
interlock system coordinates with its subsystems to carry out the protection actions according to the failure risk 
level and the preset failure handling mechanism. The WINCC monitor screen displays the operating status and 
fault information of each subsystem. The EPICS CA protocol and S7 nodave driver are used to realize the soft 
IOC reading PLC variables, and combined with C# programming to realize the control of the access system of the 
HL-2M hall. The central safety interlock system has been deployed, with an average scanning period of 1~3ms, 
which meets the safety interlock protection requirements in the first plasma discharge of HL-2M tokamak. 

Key words: HL-2M tokamak, Safety interlock, PLC 